The AQ255 and AQ257 family of AQUATROL Expansion Zoning panels work with AQ2000 Boiler Control Panels and AQ1000 Communicating Thermostats to control up to 4 space heating zones (or 8, for the AQ2558P2X Panel). Can be combined with additional expansion zoning panels and an AQ2000 control panel for a total of 16 space heating zones.
• AQ255 for zoning with pumps or zone valves without end switches.
• Auto
test function to test zones at system start up. It allows for operator
controlled testing of zones; includes pause/restart capability.
• LED lights for visual diagnostic of zone operation.
• Allows zoning with either "Normally Open" or "Normally Closed" zone valves.
• Adjacent
zoning panels can operate different zone equipment - one panel may
control 4 pumps while another may control 4 zone valves.
• Easily
switch from zone valves to pumps with same zoning module - just flip
one DIP switch. Ensure correct voltage is applied to all zone equipment
on a panel (120 Vac for pumps, 24 Vac for valves)
• R-C transformer and B-B data bus terminal connections (network communication) for easy expansion.
• Zones
can be set to energize a group pump via Aux Out dry contacts on main
control panel (AQ250, AQ25A, AQ251, AQ252) or expansion control panel
(AQ254).
• Zone synchronization through Zone of Greatest Demand control.
• 38 VA Transformer with self resetting electronic fuse.
| Application |
Zoning control for hydronic zoning system |
|
Thermostat Compatibility |
AQ1000 Series 2-wire communicating thermostats and most digital thermostats |
|
User Interface (Setting, Programming) |
DIP Switches |
|
Number of Communicating Zones Controlled |
4 |
|
R-C Input (on Control and Zoning Modules) |
24 Vac Class II (input on Control and Zoning Modules) |
|
B-B Communication Bus Terminals |
Low voltage, Class II, 2-wire polarity-insensitive, digital communicating link to other Control or Zoning modules. |
|
Zone Module Thermostat input |
Low voltage, Class II, 2-wire polarity-insensitive, digital communicating with power link to AQ1000 series thermostat. |
|
Zone Output Contact Rating |
120 Vac/250 Vac, 5A, 1/3 HP |
|
Control and Zoning Panel Temperature Rating (F) |
32 F to 130 F |
|
Control and Zoning Panel Temperature Rating (C) |
0 C to 55 C |
|
Operating Humidity Range (% RH) |
5 to 90% RH, non-condensing |
|
Dimensions (in.) |
9 1/2 in wide x 8 in. high x 3 3/8 in. deep |
|
Dimensions (mm) |
24 cm wide x 20.3 cm high x 8.5 cm deep |
|
Tradeline Value |
Tradeline |
|
Type of Zoning Devices Controlled |
Zone pumps or 2-wire valves (line voltage) |
|
Electrical Connections (Line Voltage) |
Wire-clamp screw terminals, Maximum 2 x 14 AWG each on line voltage terminals |
|
Replacement Parts |
AQ15540B 4-zone pump expansion module |
|
Approvals, Canadian Standards Association |
Certified, File No. LR76030 |